Tahanan ( R ) dan reaktansi ( XL ) penghantar AAC tegangan 20 kV
(SPLN 64: 1985)
Luas Penampang mm2
|
Jari2mm
|
Urat
|
GMR (mm)
|
Impedansi urutan positif (Ohm / km)
|
Impedansi urutan Nol (Ohm / km)
|
16
|
2,2563
|
7
|
1,6380
|
1,8382 + j 0,4035
|
1,9862 + j 1,6910
|
25
|
2,8203
|
7
|
2,0475
|
1,1755 + j 0,3895
|
1,3245 + j 1,6770
|
35
|
3,3371
|
7
|
2,4227
|
0,8403 + j 0,3791
|
0,9883 + j 1,6666
|
50
|
3,9886
|
7
|
2,8957
|
0,5882 + j 0,3677
|
0,7362 + j 1,6552
|
70
|
4,7193
|
7
|
3,4262
|
0,4202 + j 0,3572
|
0,5682 + j 1,6447
|
95
|
5,4979
|
19
|
4,1674
|
0,3096 + j 0,3464
|
0,4576 + j 1,6339
|
120
|
6,1791
|
19
|
4,6837
|
0,2451 + j 0,3375
|
0,3931 + j 1,6250
|
150
|
6,9084
|
19
|
5,2365
|
0,1961 + j 0,3305
|
0,3441 + j 1,6180
|
185
|
7,6722
|
19
|
5,8155
|
0,1590 + j 0,3239
|
0,3070 + j 1,6114
|
240
|
8,7386
|
19
|
6,6238
|
0,1225 + j 0,3157
|
0,2705 + j 1,6032
|
Tahanan ( R ) dan reaktansi ( XL ) penghantar AAAC tegangan 20 kV
(SPLN 64: 1985)
(SPLN 64: 1985)
Luas Penampang (mm2)
|
Jari2mm
|
Urat
|
GMR (mm)
|
Impedansi urutan positif (Ohm / km)
|
Impedansi urutan Nol (Ohm / km)
|
16
|
2,2563
|
7
|
1,6380
|
2,0161 + j 0,4036
|
2,1641 + j 1,6911
|
25
|
2,8203
|
7
|
2,0475
|
1,2903 + j 0,3895
|
1,4384 + j 1,6770
|
35
|
3,3371
|
7
|
2,4227
|
0,9217 + j 0,3790
|
1,0697 + j 1,6665
|
50
|
3,9886
|
7
|
2,8957
|
0,6452 + j 0,3678
|
0,7932 + j 1,6553
|
70
|
4,7193
|
7
|
3,4262
|
0,4608 + j 03572
|
0,6088 + j 1,6447
|
95
|
5,4979
|
19
|
4,1674
|
0,3096 + j 0,3449
|
0,4876 + j 1,6324
|
120
|
6,1791
|
19
|
4,6837
|
0,2688 + j 0,3376
|
0,4168 + j 1,6324
|
150
|
6,9084
|
19
|
5,2365
|
0,2162 + j 0,3305
|
0,3631 + j 1,6180
|
185
|
7,6722
|
19
|
5,8155
|
0,1744 + j 0,3239
|
0,3224 + j 1,6114
|
240
|
8,7386
|
19
|
6,6238
|
0,1344 + j 0,3158
|
0,2824 + j 1,6034
|
Tahanan, induktansi dan kapasitansi kabel isolasi XLPE:
N2XSEKBY/NA2XSEKBY tegangan 12 / 20 kV.
(IEC. 502)
N2XSEKBY/NA2XSEKBY tegangan 12 / 20 kV.
(IEC. 502)
∑ peng hantar
|
Penghantar
|
Tahanan maks pada DC temp 200C
|
Tahanan pada AC temp 900C
|
saat operasi
|
Maks kapasitas arus temp 300C
|
Arus hub singkat selama 1 detik
|
Teg nom. prcbn
| |||
Luas pnmpg
|
Cu /Al
|
Induktansi (L)
|
Kapasitansi (C)
|
dlm tanah
|
di udara
| |||||
mm2
|
Ohm/km
|
Ohm/km
|
mH/km
|
mF/km
|
Amp
|
Amp
|
kA
| kV/5 min | ||
3
|
35
|
CU
|
0,5240
|
0,6680
|
0,520
|
0,131
|
164
|
173
|
5,01
|
30
|
Al
|
0,8680
|
1,1130
|
0,520
|
0,131
|
127
|
139
|
3,29
|
30
| ||
3
|
50
|
Cu
|
0,3870
|
0,4940
|
0,497
|
0,143
|
194
|
206
|
7,15
|
30
|
Al
|
0,6410
|
0,8220
|
0,497
|
0,143
|
148
|
161
|
4,70
|
30
| ||
3
|
70
|
Cu
|
0,2680
|
0,3420
|
0,467
|
0,162
|
236
|
257
|
10,01
|
30
|
Al
|
0,4430
|
0,5680
|
0,467
|
0,162
|
179
|
204
|
6,58
|
30
| ||
3
|
95
|
Cu
|
0,1930
|
0,2470
|
0,445
|
0,180
|
283
|
313
|
13,59
|
30
|
Al
|
0,3200
|
0,4110
|
0,445
|
0,180
|
214
|
242
|
8,93
|
30
| ||
3
|
120
|
Cu
|
0,1530
|
0,1960
|
0,430
|
0,195
|
322
|
360
|
17,16
|
30
|
Al
|
0,2530
|
0,3250
|
0,430
|
0,195
|
246
|
292
|
11,28
|
30
| ||
3
|
150
|
Cu
|
0,1240
|
0,1590
|
0,414
|
0,213
|
362
|
410
|
21,45
|
30
|
Al
|
0,2060
|
0,2650
|
0,414
|
0,213
|
264
|
313
|
14,10
|
30
| ||
3
|
185
|
Cu
|
0,0991
|
0,1280
|
0,404
|
0,227
|
409
|
469
|
26,46
|
30
|
Al
|
0,1640
|
0,2110
|
0,404
|
0,227
|
308
|
365
|
17,39
|
30
| ||
3
|
240
|
Cu
|
0,0754
|
0,0980
|
0,382
|
0,263
|
474
|
553
|
34,32
|
30
|
Al
|
0,1250
|
0,1620
|
0,382
|
0,273
|
358
|
425
|
22,56
|
30
| ||
3
|
300
|
Cu
|
0,0601
|
0,0790
|
0,376
|
0,276
|
533
|
629
|
42,90
|
30
|
Al
|
0,1000
|
0,1300
|
0,376
|
0,276
|
398
|
481
|
28,20
|
30
|
Impedansi Kabel Tanah Dengan Penghantar Al
A
(mm2)
|
R
(Ω/km)
|
L
(mH/km)
|
C
(mf/km)
|
Impedansi urutan positif
(Ω /km)
|
Impedansi urutan Nol
(Ω/km)
|
150
|
0,206
|
0,33
|
0,26
|
0,206 + j 0,104
|
0,356 + j 0,312
|
240
|
0,125
|
0,31
|
0,31
|
0,125 + j0,097
|
0,275 +j0,029
|
300
|
0,100
|
0,30
|
0,34
|
0,100 + j0,094
|
0,250 + j0,282
|
bisa mnta bantuannya pak, mnta file spln 64 ke betsaniza@gmail.com. tks
BalasHapusbro maksud impedansi urutan nol dan impedansi urutan positif itu apa
BalasHapusTrimakasih kawan atas infonya
BalasHapusassalam,
BalasHapussalam kenal,. mas tolong kirimin Impedansi Kabel Tanah Dengan Penghantar Al dan CU, yang penampangnya dari 16-240mm, lagi perlu banget buat menyelesaikan tugas akhir. kirimi sumber nya ya mas,
shatoe_im@ymail.com
081958291772
tolong ya..
mksh
mas itu dapet sumbernya dari mana ya? aku udah cari spln tentang impedansi urutan positif dan nol kok ga ketemu ya?
BalasHapuskalo bisa, boleh minta sumber aslinya yg bentuk pdf gak mas?
kirim ke e-mail : maratus.s94@gmail.com
terima kasih :)
salam kenal, saya Alex Munandar. sebelumnya saya ucapkan terimakasih untuk informasinya. mas, saya mahasiswa tingkat akhir yang sedang meneliti tentang saluran kabel udara tegangan menengah. mas, saya boleh minta data dimensional dan elektris dari kabel tegangan menengah yang digunakan PLN ? kalo bisa tolong kirim ke alex00irsad@gmail.com . terimakasih mas,
BalasHapusslm knl jga mas, trma ksh bnyk ats info impdnsi2nya,
BalasHapusKlo blh mnta tlong, ad gk mas impednsi urtn postf ngtf dn nol utk kawat ACSR dan A3CS uk. 35 Smpai 350 mm nya mas...??
sama nih saya juga perlu A3CS, apa udah dapet belum bro?
HapusMas, saya minta tolong kasih impedansi kawat ACSR segala ukuran kalo ada. Saya butuh banget mas, buat Tugas Akhir. Semoga ilmu panjenengan bermanfaat. Terima Kasih.
BalasHapusNiki WA ne kulo
085640035107
maksih bos buat infonya
BalasHapusni yang butuh info tambahan lain
http://boneklistrik.blogspot.co.id/2015/07/impedansi-kawat-penghantar-menurut-spln.html
Mas minta tolong kalo ada impedansi kawat ACSR segala ukuran. Berhubung untuk Tugas Akhir minta tolong ya mas kalau ada
BalasHapusTerimakasih